Frequently Asked Questions

REACT Systems

QuestionWhen you select a room the graph has no scale.
AnswerYou need to select an input at the top of the graph, once selected it will start to flash and the relevant scale will appear.
QuestionNo temperatures are updating and a room graph inputs are showing as a flat line.
AnswerThe Modbus server could have been unknowingly shut down.
AnswerThe PC has ran out of disk space.
AnswerThe network cable has been severed.

As long as the software is still running an alarm should be initiated after a couple of hours of a signal input showing a flat reading (no change).

QuestionCan you get an alarm to re-initiate after a while if the area is still in alarm.
AnswerYes by selecting Alarm Re-Enable in the point configuration.